Good Catch Bulletin: Energized 277V Lighting Circuit Identified During Demolition
Summary
We want to recognize a strong Good Catch from the field involving an energized 277V normal lighting circuit found within the demolition scope. The circuit had not been properly air-gapped or capped, and the load-side conductors from the wall stub were left coiled without wire nuts or tape. This created a serious potential exposure during work.
Key Takeaway: Existing electrical systems must be treated as energized until they are tested, verified, and made safe.
What Happened
While extending conduits beyond the future soffit, the employee followed our Touch It, Test It policy and used a pen tester to verify the wires were de-energized before proceeding. The tester indicated the circuit was still live. Work stopped immediately, and the team coordinated with the General Contractor and hospital staff to shut off power and remove the hazard safely.
What Went Right
- The employee did not assume the circuit was safe.
- The “Touch It, Test It” policy was followed before work continued.
- The hazard was identified before contact or injury occurred.
- Work was stopped immediately when the energized condition was discovered.
- The team coordinated the proper shutdown before continuing work.
Field Expectations
- Never assume existing electrical systems are de-energized.
- Always follow “Touch It, Test It” before handling or working near electrical conductors.
- Verify circuits are properly made safe before demolition or renovation work begins.
- Stop working immediately if an unexpected, energized condition is identified.
- Communicate the hazard and coordinate the proper shutdown before resuming work.
Safety Reminder
This is exactly why we verify before we touch. When working around existing electrical systems, especially in demolition or renovation areas, we must confirm circuits are de-energized, properly capped, and made safe before work begins.
Recognition
Great job by the team for taking the time to test, stop work, communicate the hazard, and ensure the condition was corrected before continuing. This is the type of awareness and follow-through that prevents serious injuries.